For a linear high-speed CAN or CAN FD trunk built with nominal 120 Ω twisted pair, place one 120 Ω differential termination at each physical end. A standard end uses one resistor. A split end uses two matched nominal 60 Ω resistors in series with a capacitor from their midpoint to the designated reference. Both present roughly the same end-to-end DC resistance. The choice changes how the circuit handles high-frequency common-mode noise.
A useful first question on the bench is which two devices actually sit at the cable ends? Trace the harness before changing a board jumper. Low-speed fault-tolerant CAN and single-wire CAN use different physical layers and are outside this guide.
Cover photo by Liz Clark / Adafruit, CC BY-SA 3.0 (resized and compressed).
Characteristic Impedance vs. DC Resistance
During a fast voltage transition, the traveling wave sees the cable’s characteristic impedance. An end load close to that impedance reduces reflections. A multimeter instead measures DC resistance after the circuit has settled. Its reading across an assembled, unpowered network can help you count connected loads, but it cannot measure cable characteristic impedance. See the NI CAN physical layer and termination guide.
Standard vs. Split Termination
Standard termination places a single nominal 120 Ω resistor directly between CANH and CANL at each physical end of the linear trunk, not at every node. TI illustrates the two end loads in SLLA270, Figure 8. If an endpoint device is removable, check whether unplugging it also removes the terminator.

Split termination replaces one end’s 120 Ω resistor (or both ends, depending on system EMC design) with two matched nominal 60 Ω resistor arms in series, plus a midpoint capacitor tied to a reference ground. As shown in TI SLLA270, Section 4.5.2, the differential bus still sees 120 Ω, while the midpoint capacitor forms a low-pass filter that shunts high-frequency common-mode noise.

Split termination is not a universal EMC fix. Its filtering benefit depends on tightly matched resistor arms and a clean, low-impedance ground return. If the reference plane carries switching noise, suffers large ground-potential offsets between nodes, or uses mismatched arm values, split termination can degrade differential symmetry and couple noise onto the bus instead of removing it.
Unpowered Meter Check and Worked Example
Before checking termination with a multimeter, power down every node and allow bus capacitance to discharge. Disconnect any powered analyzer or interface. Keep the intended termination loads connected, verify that there is no residual voltage, then measure resistance between CANH and CANL.

Worked example (assumed nominal 120 Ω ends, negligible cable DC resistance, healthy transceivers):
- Two ends terminated (healthy baseline): Two 120 Ω loads in parallel yield (120 × 120) / (120 + 120) = 60 Ω. A split end (60 Ω + 60 Ω in series) still measures 120 Ω alone and ~60 Ω in parallel with the opposite 120 Ω end.
- One end terminated: Measures ~120 Ω, consistent with a missing or open terminator, or a cable break that isolates the far end.
- Three termination loads connected: Three 120 Ω resistors in parallel yield 120 / 3 = 40 Ω, typically caused by an enabled terminator on an intermediate node.

Treat DC resistance as a coarse sanity check, not proof of signal integrity. A ~60 Ω reading cannot confirm the resistors sit at the physical trunk ends, cannot detect an open midpoint capacitor, and cannot catch excessive stub lengths. Likewise, a reading near or below ~40 Ω can stem from a partial wiring short or a damaged transceiver rather than a third resistor.
Check a two-end resistance calculation
For two connected end loads, use R₁ × R₂ / (R₁ + R₂). For example, a split end made from two 60.4 Ω arms totals 120.8 Ω. With a standard 120 Ω end, the expected reading is about 60.2 Ω before lead, cable and component tolerances.
What belongs on the termination BOM?
Before releasing your BOM, confirm these parameters against your transceiver datasheet and environmental requirements:
| BOM Item | Key Parameters to Lock Down |
|---|---|
| Standard Termination Resistor | 120 Ω nominal, tolerance, power/pulse rating for bus-fault conditions, package size, temperature range and required qualification |
| Split Termination Pair + Cap | Nominal resistance and arm matching, capacitor value and voltage rating, reference return path per the transceiver application circuit |
| Enable/Disable Hardware | Jumper, DIP switch, or DNP footprint if the same PCB serves both end and mid-bus nodes |

If you are still finalizing your physical-layer IC pairing alongside passive termination, review our guide on CAN controller vs. transceiver to confirm whether your board needs a discrete transceiver before locking the BOM. Compare candidates in the CAN transceiver IC catalog.
Once your resistor values, matching tolerances, and package grades are defined, you can source standard 120 Ω resistors, matched 60 Ω split-termination pairs, and midpoint capacitors together with your CAN transceivers. When you are ready for pricing or availability verification, submit your CAN BOM or RFQ to ApexComponent with full manufacturer part numbers (including packaging and temperature suffixes), target quantities, required grade, and whether approved alternates are acceptable.